Introduction
A beam almost always has enough strength long before it has enough stiffness. Deflection governs the size of most floor beams, purlins and lintels in ordinary building work, and it is checked against serviceability criteria rather than strength limits.
The formulas here are elastic and assume linear behaviour, a prismatic section and loads applied within the elastic range — all normally true at serviceability load levels.
The standard results
Every deflection formula has the same shape: a load term, a length term raised to the third or fourth power, divided by E and I. Because length is raised to the fourth power for distributed loads, span drives deflection far more aggressively than load does.
For a simply supported beam under UDL, δ = 5wL⁴/(384EI). For a central point load, δ = PL³/(48EI). For a cantilever with an end load, δ = PL³/(3EI).
Serviceability limits
Australian practice expresses deflection limits as a fraction of span: L/250 for general members where no specific criterion is set, L/360 or tighter where finishes or cladding are sensitive, and tighter again for brittle finishes or where ponding is a risk.
AS 4100 does not itself impose a single deflection limit; serviceability requirements come from AS/NZS 1170.0 and, more often, from the project specification, the client and the cladding supplier. Always confirm which limit applies before reporting a pass.
- Check total deflection for permanent plus long-term imposed load, and incremental deflection for the cladding.
- Deflection of a cantilever is measured at the tip, not at mid-length.
- Long spans in light sections are stiffness-driven, not strength-driven.
- Floor vibration is a separate serviceability issue from static deflection.
When deflection governs the design
If deflection controls, the efficient answer is depth. Increasing a section’s depth raises I by the cube of the change, while adding width raises it linearly and adds mass proportionally.
A fabricated plate girder, a deeper rolled section, or a change of structural system (adding a prop, shortening the span) usually beats simply picking the next heavier section.
[F]Technical formulas
Simply supported, UDL
δ = 5wL⁴ / (384EI)
w in N/mm, L in mm, E in MPa, I in mm⁴ → δ in mm.
Simply supported, central point load
δ = PL³ / (48EI)
Point load at midspan.
Cantilever, end point load
δ = PL³ / (3EI)
Measured at the free end.
Deflection ratio
ratio = L / δ
Compare with the specified limit such as L/250.
[V]Explanation of variables
| Symbol | Meaning | Unit |
|---|---|---|
| δ | Maximum deflection | mm |
| w | Serviceability UDL | N/mm (= kN/m) |
| P | Serviceability point load | N |
| E | Young’s modulus (200 000 MPa for steel) | MPa |
| I | Second moment of area | mm⁴ |
[E]Worked example
Deflection of a 6 m span carrying 10 kN/m
- 01Take w = 10 kN/m = 10 N/mm, L = 6 000 mm, E = 200 000 MPa, I = 45 × 10⁶ mm⁴.
- 02δ = 5 × 10 × 6 000⁴ / (384 × 200 000 × 45 × 10⁶).
- 03Numerator = 5 × 10 × 1.296 × 10¹⁵ = 6.48 × 10¹⁶. Denominator = 3.456 × 10¹⁵.
- 04δ = 18.75 mm, which is span / 320.
Result
The beam satisfies a L/250 limit but fails a L/360 limit for brittle finishes. The number, not the formula, decides the outcome.
[A]Practical applications
- Checking a floor beam against a specified deflection criterion.
- Sizing a lintel over a wide opening in masonry.
- Comparing two candidate sections where strength is not the driver.
- Investigating visible sag in an existing structure.
[!]Common mistakes
- Feeding factored loads into a serviceability deflection calculation.
- Entering the span in metres into a formula that expects millimetres.
- Comparing midspan deflection on a cantilever, where the tip governs.
- Quoting a deflection without stating which limit it was checked against.
[S]References and sources
- AS/NZS 1170.0 – Structural design actions: general principlesServiceability limit state framework.
- AS 4100 – Steel structuresMember design; deflection criteria are specified separately.
Standards are cited by designation and title only — no clause text is reproduced. Purchase current editions from Standards Australia, and confirm the edition that applies to your project.