Introduction
Three-phase power delivers √3 times the power of three single-phase circuits of the same current, because the three phases share a neutral return and their instantaneous powers add rather than cancel.
The gap between the power actually used (kW) and the power the supply must carry (kVA) is power factor — and it is the reason an undersized cable can serve a load that looks fine on a kilowatt rating.
The basic relationship
Real power in a balanced three-phase circuit is √3 × line voltage × line current × power factor. With 400 V, 100 A and a power factor of 0.85, the real power is 58.9 kW while the apparent power is 69.3 kVA.
Australian low-voltage distribution is nominally 230 V phase to neutral and 400 V phase to phase, consistent with AS 60038.
Power factor
Power factor is real power divided by apparent power. Motors, transformers and magnetic ballasts draw magnetising current that does no work, so current is larger than the power alone would suggest.
At 0.85 power factor the supply carries about 18 % more current than the useful power requires. At 0.7 it is 43 % more. Cables, switchgear and transformers are all sized on current, so a poor power factor is a direct capital cost.
Correction
Capacitors supply the reactive component locally so the supply carries less current. Correction is applied in steps close to the load, with care taken not to over-correct lightly loaded motors or create resonant conditions with the supply.
A capacitor bank sized from the kW, the existing power factor and the target power factor removes the reactive burden without changing the real power consumed.
[F]Technical formulas
Three-phase real power
P = √3 × V × I × cos φ
V is line-to-line voltage in volts.
Apparent power
S = √3 × V × I
Result in VA; divide by 1 000 for kVA.
Reactive power
Q = √(S² − P²)
kVAr required for correction planning.
Capacitor size
Q(c) = P × (tan φ₁ − tan φ₂)
From existing to target power factor.
[V]Explanation of variables
| Symbol | Meaning | Unit |
|---|---|---|
| P | Real power | kW |
| S | Apparent power | kVA |
| Q | Reactive power | kVAr |
| V | Line-to-line voltage | V |
| cos φ | Power factor | – |
[E]Worked example
A 100 A three-phase load at 0.85 power factor
- 01S = √3 × 400 × 100 = 69.3 kVA.
- 02P = 69.3 × 0.85 = 58.9 kW.
- 03Correcting to 0.95: Q(c) = 58.9 × (tan 31.8° − tan 18.2°) = 58.9 × (0.620 − 0.329) = 17.1 kVAr.
- 04Applying that correction reduces current by about 10 % for the same real power.
Result
About 17 kVAr of capacitors removes the reactive component, freeing capacity in the existing cable and switchgear.
[A]Practical applications
- Converting a motor nameplate rating into an operating current.
- Checking whether a supply has capacity for an additional load.
- Sizing power factor correction equipment.
- Understanding a utility bill with a reactive power charge.
[!]Common mistakes
- Using kW and kVA interchangeably.
- Applying the √3 factor to a single-phase calculation.
- Over-correcting a plant that runs lightly loaded at night.
- Ignoring power factor when converting kW to current.
[S]References and sources
- AS/NZS 3000 – Electrical installations (known as the Australian/New Zealand Wiring Rules)Installation requirements for low-voltage work.
- AS 60038 – Standard voltagesNominal system voltages used in Australian distribution.
Standards are cited by designation and title only — no clause text is reproduced. Purchase current editions from Standards Australia, and confirm the edition that applies to your project.