Introduction
A calculation is not finished when the answer appears; it is finished when someone else can follow it and reach the same answer. This example sets out a full check in that order, including the step where the first trial section is rejected.
The numbers are simplified to show method, not to replace a design check against the current edition of AS 4100.
Step 1 — Define the actions
A simply supported floor beam spans 6.0 m with a uniformly distributed action of 12 kN/m at the strength limit state and 8 kN/m at the serviceability limit state.
Stating both values up front prevents the classic error of using factored loads in a deflection check, which overstates deflection and leads to needlessly heavy sections.
Step 2 — Analyse
Design moment M* = wL²/8 = 12 × 36 / 8 = 54 kN·m. Design shear V* = wL/2 = 36 kN. Both act at midspan and at the supports respectively.
Step 3 — Strength
For a compact, laterally restrained section, the bending capacity is approximately φMs = 0.9 × fy × Z. With fy = 300 MPa and a trial Z = 250 × 10³ mm³: Ms = 75 kN·m and φMs = 67.5 kN·m.
Since 67.5 > 54, the trial section passes in bending with a utilisation of 0.80. Shear capacity is checked separately and is rarely critical for a uniformly loaded floor beam of this span.
Step 4 — Serviceability, where the trial fails
Using the unfactored 8 kN/m and a trial I = 30 × 10⁶ mm⁴: δ = 5 × 8 × 6 000⁴ / (384 × 200 000 × 30 × 10⁶) = 22.5 mm, which is L/267.
Against a L/250 limit that passes; against a L/360 limit for a tiled floor it fails. The fix is depth, not mass: a section with I ≈ 110 × 10⁶ mm⁴ gives 6.1 mm, or L/980, with margin to spare.
[F]Technical formulas
Design moment
M* = w* × L² / 8
w* is the factored UDL.
Bending capacity
φMs = 0.9 × fy × Z
Simplified; section slenderness and restraint must be checked.
Utilisation
M* / φMs
Must not exceed 1.0.
Serviceability deflection
δ = 5w(service)L⁴ / (384EI)
Always use unfactored loads.
[V]Explanation of variables
| Symbol | Meaning | Unit |
|---|---|---|
| M* | Design bending moment | kN·m |
| φMs | Design section bending capacity | kN·m |
| fy | Yield stress of the steel grade | MPa |
| Z | Section modulus about the bending axis | mm³ |
| w(service) | Unfactored serviceability load | kN/m |
[E]Worked example
The check as it is reported
- 01Actions: w* = 12 kN/m (strength), 8 kN/m (serviceability).
- 02M* = 54 kN·m; V* = 36 kN.
- 03Bending: φMs = 67.5 kN·m → utilisation 0.80, OK.
- 04Deflection: δ = 22.5 mm = L/267 → fails a L/360 criterion; adopt a deeper section (I ≈ 110 × 10⁶ mm⁴, δ ≈ 6.1 mm = L/980).
Result
One page, four steps, one rejected trial and a clear reason for the final section. That is what a reviewer needs, and what a certifier can rely on.
[A]Practical applications
- Preparing a calculation sheet for certification.
- Checking a supplier’s proposed beam substitution.
- Teaching the difference between strength and serviceability checks.
- Recording a design decision so it can be revisited later.
[!]Common mistakes
- Using factored loads in the deflection check.
- Omitting the load case that actually governs — often a point load or a cantilever.
- Failing to check lateral restraint before assuming full bending capacity.
- Presenting a final section without showing that a lighter one failed.
[S]References and sources
- AS 4100 – Steel structuresSection capacity, member capacity and restraint requirements.
- AS/NZS 1170.1 – Structural design actions: permanent, imposed and other actionsLoad factors and combinations used to derive w*.
Standards are cited by designation and title only — no clause text is reproduced. Purchase current editions from Standards Australia, and confirm the edition that applies to your project.