[ENGINEERING CALCULATIONS]

A Complete Worked Example: Documenting a Steel Beam Check

One beam, checked end to end — actions, bending, shear, deflection — set out the way a reviewer needs to see it, including the stage where the trial section fails.

8 MIN READ4 SECTIONS

Introduction

A calculation is not finished when the answer appears; it is finished when someone else can follow it and reach the same answer. This example sets out a full check in that order, including the step where the first trial section is rejected.

The numbers are simplified to show method, not to replace a design check against the current edition of AS 4100.

Step 1 — Define the actions

A simply supported floor beam spans 6.0 m with a uniformly distributed action of 12 kN/m at the strength limit state and 8 kN/m at the serviceability limit state.

Stating both values up front prevents the classic error of using factored loads in a deflection check, which overstates deflection and leads to needlessly heavy sections.

Step 2 — Analyse

Design moment M* = wL²/8 = 12 × 36 / 8 = 54 kN·m. Design shear V* = wL/2 = 36 kN. Both act at midspan and at the supports respectively.

Step 3 — Strength

For a compact, laterally restrained section, the bending capacity is approximately φMs = 0.9 × fy × Z. With fy = 300 MPa and a trial Z = 250 × 10³ mm³: Ms = 75 kN·m and φMs = 67.5 kN·m.

Since 67.5 > 54, the trial section passes in bending with a utilisation of 0.80. Shear capacity is checked separately and is rarely critical for a uniformly loaded floor beam of this span.

Step 4 — Serviceability, where the trial fails

Using the unfactored 8 kN/m and a trial I = 30 × 10⁶ mm⁴: δ = 5 × 8 × 6 000⁴ / (384 × 200 000 × 30 × 10⁶) = 22.5 mm, which is L/267.

Against a L/250 limit that passes; against a L/360 limit for a tiled floor it fails. The fix is depth, not mass: a section with I ≈ 110 × 10⁶ mm⁴ gives 6.1 mm, or L/980, with margin to spare.

[F]Technical formulas

Design moment

M* = w* × L² / 8

w* is the factored UDL.

Bending capacity

φMs = 0.9 × fy × Z

Simplified; section slenderness and restraint must be checked.

Utilisation

M* / φMs

Must not exceed 1.0.

Serviceability deflection

δ = 5w(service)L⁴ / (384EI)

Always use unfactored loads.

[V]Explanation of variables

SymbolMeaningUnit
M*Design bending momentkN·m
φMsDesign section bending capacitykN·m
fyYield stress of the steel gradeMPa
ZSection modulus about the bending axismm³
w(service)Unfactored serviceability loadkN/m

[E]Worked example

The check as it is reported

  1. 01Actions: w* = 12 kN/m (strength), 8 kN/m (serviceability).
  2. 02M* = 54 kN·m; V* = 36 kN.
  3. 03Bending: φMs = 67.5 kN·m → utilisation 0.80, OK.
  4. 04Deflection: δ = 22.5 mm = L/267 → fails a L/360 criterion; adopt a deeper section (I ≈ 110 × 10⁶ mm⁴, δ ≈ 6.1 mm = L/980).

Result

One page, four steps, one rejected trial and a clear reason for the final section. That is what a reviewer needs, and what a certifier can rely on.

[A]Practical applications

  • Preparing a calculation sheet for certification.
  • Checking a supplier’s proposed beam substitution.
  • Teaching the difference between strength and serviceability checks.
  • Recording a design decision so it can be revisited later.

[!]Common mistakes

  • Using factored loads in the deflection check.
  • Omitting the load case that actually governs — often a point load or a cantilever.
  • Failing to check lateral restraint before assuming full bending capacity.
  • Presenting a final section without showing that a lighter one failed.

[S]References and sources

  • AS 4100 – Steel structuresSection capacity, member capacity and restraint requirements.
  • AS/NZS 1170.1 – Structural design actions: permanent, imposed and other actionsLoad factors and combinations used to derive w*.

Standards are cited by designation and title only — no clause text is reproduced. Purchase current editions from Standards Australia, and confirm the edition that applies to your project.