Introduction
Tank shell thickness is set by the pressure of the product at each course, not by the size of the tank alone. A tall tank with a light product and a short tank with a heavy product can need the same plate at the bottom course.
For an atmospheric storage tank the calculation is short, but the thickness you specify is usually decided by corrosion allowance, minimum plate rules and handling, not by the pressure term.
The pressure term
Hydrostatic pressure rises linearly with depth: p = ρ g h. In a shell course, the design head is taken to the bottom of that course, which is why the bottom shell course is always the thickest and the top course the thinnest.
The 1-foot method in API 650 takes the design head to 0.3 m above the bottom of each course, on the basis that the course above restrains the one below. The result is a shell thickness in millimetres for a given diameter, head, specific gravity and allowable stress.
What usually governs
Once the pressure term is calculated, corrosion allowance is added — commonly 1.5 mm to 3 mm for water and fuel duty, more for aggressive chemicals. A calculated 3.6 mm shell becomes 6.6 mm with a 3 mm allowance, and then rounds up to the next available plate.
Minimum thickness rules, nozzle reinforcement and the need to weld without distortion then take over. On small tanks the pressure term is almost irrelevant; on large ones it dominates the lower courses.
- Calculate each course separately — a single thickness for the whole shell is either wasteful or unsafe.
- Round up to a plate thickness that is actually rolled and supplied.
- State the corrosion allowance and the design specific gravity on the drawing.
- Check the shell to bottom and shell to roof junctions separately.
[F]Technical formulas
Hydrostatic pressure
p = rho x g x h
rho in kg/m3, h in m gives Pa.
Shell thickness (1-foot method)
t = 4.9 x D x (H - 0.3) x G / Sd + CA
D and H in m, Sd in MPa, result in mm.
Hoop stress check
sigma = p x D / (2 x t)
Sanity check on the thickness chosen.
[V]Explanation of variables
| Symbol | Meaning | Unit |
|---|---|---|
| D | Tank diameter | m |
| H | Design liquid level above the course | m |
| G | Design specific gravity of the product | - |
| Sd | Allowable design stress | MPa |
| CA | Corrosion allowance | mm |
[E]Worked example
10 m diameter water tank, 12 m to the design level
- 01Design head for the bottom course: H - 0.3 = 11.7 m, with G = 1.0.
- 02t = 4.9 x 10 x 11.7 x 1.0 / 160 = 3.58 mm.
- 03Add a 3 mm corrosion allowance: 6.58 mm.
- 04Round up to the next rolled plate: specify 8 mm for the bottom course.
Result
The pressure term gives 3.6 mm; the corrosion allowance and plate availability decide the 8 mm actually specified.
[A]Practical applications
- Setting shell courses for a new atmospheric storage tank.
- Checking whether an existing tank can hold a denser product.
- Pricing a tank by plate mass before detailed design.
- Reviewing a fabricator quotation that quotes one thickness for the whole shell.
[!]Common mistakes
- Using the total tank height for every course instead of the head at that course.
- Forgetting the corrosion allowance, or adding it after rounding down.
- Using specific gravity 1.0 for a product that is heavier than water.
- Treating a thin shell as a plate bending problem instead of a membrane problem.
[S]References and sources
- AS 1692 – Steel tanks for flammable and combustible liquidsAustralian requirements for shop and field built tanks.
- API 650 – Welded tanks for oil storageSource of the 1-foot method used above.
Standards are cited by designation and title only — no clause text is reproduced. Purchase current editions from Standards Australia, and confirm the edition that applies to your project.
FABRICATION AND PROJECTS
From the volume to the fabricated tank
Capacity and level figures feed straight into shell design, nozzle schedules, bunding and freight planning. These resources cover the fabrication and project side of the same work.